Material Shape
Round Wire
Range of Application
Flame Retardant
Certification
ISO9001, CCC
Dielectric Strength
2.5kv
Transport Package
100m/Roll, 305m/Roll
Specification
2.5mm2, 4mm2, 6mm2, 10mm2
Standard building Wires & Cables Cable THW-90 6mm2 10 mm2Standard wires & cables <1kV
THW-90 450/750 V less than or equal to 10 mm2
DescriptionGeneral application in fixed installations, resistant to humidity and heat.
STANDARDInternational: IEC 60228
National: NTP 370,252; NTP-IEC 60228; UL 2556
DESCRIPTION
Application:In fixed installations, in buildings, inside premises with a dry or humid environment, control panel connections and, in general, in all installations that require greater current capacity to the TW-80 cable.
Construction:1. Conductor: Compressed soft copper, class 2.
2. Insulation: Double layer PVC compound.
Main features:Good dielectric strength, resistance to moisture, grease, oil and heat up to service temperature. Does not spread VW-1 flame.
Section:From 2.5 mm2 to 10 mm2.
Packaging:From 2.5 mm2 to 6 mm2 in 100 meter rolls.
10 mm2 cables on reels.
cable thw Colour:At the request of the client.
ELECTRICAL CHARACTERISTICSNominal operating voltage Uo / U (Um) | 450/750 V |
Dielectric strength | 2.5kV |
Dielectric Rigidity Time Vac to insulation | 5min |
CHARACTERISTICS OF USEMaximum operating temperature | 90 ° C |
Emergency overload temperature | 130 ° C |
Maximum short-circuit conductor temperature | 250 ° C |
cable thw DIMENSIONName | Section | Diam. Conductor (mm) | Insulation Thickness (mm) | Cable Diameter (mm) | Approx. Weight (kg/km) |
THW-90 2,5 mm2 | 2.5 | 1.9 | 0.8 | 3.6 | 32 |
THW-90 4 mm2 | 4 | 2.4 | 0.8 | 4.1 | 47 |
THW-90 6 mm2 | 6 | 3.0 | 0.8 | 4.7 | 67 |
THW-90 10 mm2 | 10 | 3.7 | 1.1 | 6.0 | 111 |